Active AS-i module bus system AS-Interface.
This is a new surplus item and it comes in the original package.
Collapse all categories
Product characteristics |
Active AS-i module |
Mounting on DIN rail |
Combicon connection |
String mounting possible |
Addressing socket |
Input supply from external PELV voltage source |
Version 2.1 with extended addressing mode |
Digital inputs |
Electrical data |
Electrical design |
|
4 inputs |
Operating voltage [V] |
|
26.5...31.6 DC |
Total current consumption from AS-i [mA] |
|
< 50 |
Inputs |
Digital |
Circuit |
|
PNP |
Sensor supply |
|
via E+/E- / external to PELV |
Voltage range [V] |
|
20...30 DC |
Max. current load for all inputs total [mA] |
|
500 |
Input current High/Low [mA] |
|
6…10 / 0…2 |
Switching level High signal 1 [V] |
|
> 11 |
Short-circuit proof |
|
yes |
Environment |
Ambient temperature [°C] |
|
-25...70, cRUus: surrounding air temperature -25...60 °C |
Protection |
|
IP 20 |
Tests / approvals |
EMC |
|
EN 50295 |
MTTF [Years] |
|
486 |
AS-i classification |
AS-i version |
|
2.1 |
Extended addressing mode possible |
|
yes |
AS-i profile |
|
S-0.A.E |
I/O configuration [hex] |
|
0 |
ID code [Hex] |
|
A.E |
AS-i certificate |
|
39402 |
Data bits |
|
Data bit |
D0 |
D1 |
D2 |
D3 |
Function |
Input I1 |
Input I2 |
Inputg I3 |
Input I4 |
|
Mechanical data |
Housing materials |
|
PA |
Weight [kg] |
|
0.139 |
Displays / operating elements |
Output status indication LED |
|
yellow |
Operation LED |
|
green |
Error LED |
|
Red |
Electrical connection |
Connection |
|
Combicon |
Wiring
A+: |
AS-i + |
A-: |
AS-i - |
I+: |
Sensor supply +24V |
I-: |
Sensor supply 0V |
E+: |
External sensor supply +24V |
E-: |
External sensor supply 0V |
I1...I4: |
Switching input Sensor 1...4 |
|
|
|
Accessories |
Accessories (optional) |
|
|
Remarks |
Remarks |
|
If a slave with the ID code "A" (extended addressing mode possible) is used with a master of the first generation (version 2.0), the parameter P3 must be 1 and the output bit D3 = 0. The output bit D3 must not be used. |
|
Pack quantity [piece] |
|